A BILL TO BE ENTITLED
|
|
|
AN ACT
|
|
|
relating to the recovery of costs related to providing electricity |
|
|
service to customers at a computational load site. |
|
|
BE IT ENACTED BY THE LEGISLATURE OF THE STATE OF TEXAS: |
|
|
SECTION 1. Sections 35.004(c-1) and (c-2), Utilities Code, |
|
|
are redesignated as Section 35.0041, Utilities Code, and amended to |
|
|
read as follows: |
|
|
Sec. 35.0041. INTERCONNECTION OF AND COST RECOVERY FROM |
|
|
LARGE LOAD CUSTOMERS. (a) [(c-1)] The commission by rule shall |
|
|
ensure that a large load customer who is subject to the standards |
|
|
adopted under Section 37.0561 contributes to the recovery of the |
|
|
interconnecting electric utility's costs to interconnect the large |
|
|
load to the utility's system. |
|
|
(b) [(c-2)] An electric cooperative or municipally owned |
|
|
utility that has not adopted customer choice shall pass through to a |
|
|
large load customer who is subject to the standards adopted under |
|
|
Section 37.0561 the reasonable costs to interconnect the large load |
|
|
in a manner determined by the electric cooperative or municipally |
|
|
owned utility. |
|
|
(c) This subsection applies only to costs not recovered |
|
|
under Subsection (a) or (b). Notwithstanding Section 35.004, the |
|
|
commission by rule shall establish a system to: |
|
|
(1) ensure that transmission costs of service |
|
|
attributable to a customer receiving electricity service at a |
|
|
computational load site are allocated to a separate transmission |
|
|
cost of service rate class composed only of that type of customer; |
|
|
and |
|
|
(2) require each electric utility that provides |
|
|
distribution service to a customer described by this subsection to |
|
|
use a rate mechanism established by the commission for the purposes |
|
|
of Subdivision (1). |
|
|
(d) For purposes of Subsection (c), "computational load |
|
|
site" means one or more buildings, structures, or installations at |
|
|
a single location that: |
|
|
(1) primarily contains information technology |
|
|
infrastructure used for: |
|
|
(A) creating, executing, and delivering software |
|
|
applications and services; |
|
|
(B) artificial intelligence training, |
|
|
deployment, and delivery; |
|
|
(C) adding virtual currency transactions to a |
|
|
distributed ledger; or |
|
|
(D) other computational activities at a data |
|
|
center; and |
|
|
(2) is supplied through electrical equipment that is |
|
|
connected to the bulk power system. |
|
|
(e) In this section, "virtual currency" has the meaning |
|
|
assigned by Section 12.001, Business & Commerce Code. |
|
|
(f) The system established under Subsection (c) may include |
|
|
requirements that customers subject to that subsection pay minimum |
|
|
demand charges, operate under contract terms specified by the |
|
|
commission, or meet any other requirements the commission |
|
|
determines necessary to ensure that transmission costs of service |
|
|
attributable to those customers are not paid by other customers. |
|
|
SECTION 2. The Public Utility Commission of Texas shall |
|
|
adopt or revise rules as necessary to implement the changes in law |
|
|
made by this Act not later than September 1, 2028. |
|
|
SECTION 3. This Act takes effect immediately if it receives |
|
|
a vote of two-thirds of all the members elected to each house, as |
|
|
provided by Section 39, Article III, Texas Constitution. If this |
|
|
Act does not receive the vote necessary for immediate effect, this |
|
|
Act takes effect September 1, 2027. |